Standards

DIN, VDE 0660 part 500, IEC 439-1 and VDE 0560 part 41
Design in accordance withDIN EN60439 part 1, partially type tested combination
Construction formSteel plate cabinet for KB and ES versions
 Mounting plate for MP version
Module for MO version
power factor controllerProphi according to data sheet or selection table
Nominal voltage400V, 50Hz; other voltages upon request
Control voltage230V, 50Hz
Capacitor voltage440V at 5,67 - 7%, 525V at 14%
Voltage capacity of the capacitorat p=5,67-7%440Vat p=14%525V
8 hours each day484V 577V
30 minutes each day506V 604V
5 minutes 528V 630V
1 minute572V 682V
Power lossesCapacitors <0.3 W/kvar, units  4-7kvar
Anlagen-AusführungPermitted harmonic currentsharmonic voltage
 I250HzI350HzU250HzU350Hz
FK 5,670,565 IN0,186 IN5%5%
FK 70,31 IN0,134 IN5%5%
FK 140,086 IN0,051 IN5%5%
Capacitor protection switch cyclesMax 100,000 switch cycles
Optional thyristor actuatorUnlimited
Current transformer connection.. /1A, .. /5A
Nominal power/nominal currentRefer to option overview
Standard ratioRefer to option overview
DischargeWith discharge resistance in accordance with EN60831-1/2
Installation heightUp to 2000m above sea level
Environmental temperatureAccording to DIN EN 60439 part 1
Protection classKB, ES: IP 32 and MP, MO: IP00
CoolingSelf-ventilating or forced ventilation depending on type
ColourKB, ES: RAL 7032 bzw. RAL 7035, MP, MO: verzinkt
Noise emissions  (FK)<60dB at a distance of 1m from the closed unit
Connection diameters and fusesRefer to option overview

Bilgi: Reaktörsüz PFC-sistemleri aşağıdaki durumlarda kullanılmamalıdır:

  • Converter gücü (doğrusal olmayan yükler) > bağlantı gücünün %15'i 
  • THD-U > 3 %
  • de-tuned kondansatörlü şebekeler
  • 270-425Hz aralığında kritik ripple kontrol sistemleri
  • PFC gücü > trafo veya bağlantı gücünün %35